GLF PRODUCT SPECIFICATIONS: |
|
·
Standard Material: 304 Stainless Steel. Optional:
Galvanized Steel Sheet ·
Usable for sterility-sensitive places such as
operating rooms, chemical labs and clean rooms. ·
Laminar flow provides removal of particles and
microbes from requested area. ·
According to DIN 1946/4 and DIN 25414, especially
surgeries that require a high level of sterility fulfillment of the
conditions. 100% Leakproof tested. ·
Proper disinfection and ease of maintenance. ·
Mounted easily to all types of ceilings |

HIZLI
SEÇİM TABLOSU
|
Item |
W(mm) |
H(mm) |
L(mm) |
Air Flow (m3/h) |
Velocity m/sn |
Avarage Sound Power Level [dB] |
Pressure Loss at Start
(Pa) |
Pressure Loss at
Final(Pa) |
|
1 |
2400 |
1200 |
450 |
2400 |
0,23 |
35 |
120 |
600 |
|
2 |
2400 |
1400 |
450 |
2800 |
0,23 |
35 |
150 |
600 |
|
3 |
2400 |
1600 |
450 |
3200 |
0,23 |
30 |
110 |
600 |
|
4 |
2400 |
1800 |
450 |
3600 |
0,23 |
30 |
130 |
600 |
|
5 |
2400 |
2000 |
450 |
4000 |
0,23 |
35 |
120 |
600 |
|
6 |
2400 |
2200 |
450 |
4400 |
0,23 |
35 |
130 |
600 |
|
7 |
2400 |
2400 |
450 |
4800 |
0,23 |
35 |
150 |
600 |
|
8 |
3000 |
2400 |
450 |
6000 |
0,23 |
35 |
120 |
600 |
|
9 |
3000 |
2800 |
450 |
7000 |
0,23 |
40 |
160 |
600 |
|
10 |
3000 |
3000 |
450 |
7500 |
0,23 |
40 |
170 |
600 |